Serial Interface Operation
Eaton ePDU G3 Operation Manual P-164000277—Rev 1 www.eaton.com/ePDU 73
Environment.Input[2].State[0].Level Parameter Dry contact Config
1: Open makes just informational 0 into State.
2: Open makes Warning trap.
3: Open makes Alarm trap.
- RW
Environment.Input[2].State[1].Level Parameter Dry contact Config
1: Close makes just informational 0 into State.
2: Close makes Warning trap.
3: Close makes Alarm trap.
- RW
Environment.OverHumidity[1].Threshold Parameter d% RW
Environment.OverHumidity[2].Threshold Parameter d% RW
Environment.OverHumidity[3].Threshold Parameter d% RW
Environment.OverHumidity[4].Threshold Parameter d% RW
Environment.OverTemperature[1].Threshold Parameter d°K RW
Environment.OverTemperature[2].Threshold Parameter d°K RW
Environment.OverTemperature[3].Threshold Parameter d°K RW
Environment.OverTemperature[4].Threshold Parameter d°K RW
Environment.PresentStatus.CommunicationLost AlarmL1 0: OK
1: Communication failure with the sensor probe or probe
not present.
- RO
Environment.PresentStatus.OverHumidity AlarmL1 0: No threshold triggered
1: Warning low threshold triggered
2: Critical low threshold triggered
3: Warning high threshold triggered
4: Critical high threshold triggered
- RO
Environment.PresentStatus.OverTemperature AlarmL1 0: No threshold triggered
1: Warning low threshold triggered
2: Critical low threshold triggered
3: Warning high threshold triggered
4: Critical high threshold triggered
- RO
Environment.PresentStatus.Present Measure 0: Sensor probe never connected since F/W starts.
1 : Sensor probe connected at least 1 time since F/W
starts.
- RO
Environment.Temperature Measure Measured Temperature on environmental monitoring
probe.
It is 0 when no probe is connected.
d°K RO
PDU.DaisyChain[x].ChangedStatus.CommunicationLost Timestamp Communication with daisy chained device has failed,
datation of the alarm.
s RO
PDU.DaisyChain[x].iName String[15] Daisy chain friendly name - RO
PDU.DaisyChain[x].PresentStatus.CommunicationLost AlarmL1 Communication with daisy chained device has failed. - RO
PDU.Gang.Count Constant Number of factory groups in the PDU. - RO
PDU.Gang[x].ActivePower Measure Active Power provided by the breaker/section. For a double
pole breaker, the apparent power for the two poles is
combined.
dW RO