Serial Interface Operation
Eaton ePDU G3 Operation Manual P-164000277—Rev 1 www.eaton.com/ePDU 74
PDU.Gang[x].ApparentPower Measure Apparent Power provided by the breaker/section. For a
double pole breaker, the apparent power for the two poles
is combined.
dVA RO
PDU.Gang[x].ChangedStatus.OverCurrent Timestamp s RO
PDU.Gang[x].ChangedStatus.OverVoltage Timestamp s RO
PDU.Gang[x].ChangedStatus.SwitchOnOff Time stamp s RO
PDU.Gang[x].ConfigCurrent Constant Nominal Amps: 10A, 16A, 20A, ..
This is useful for both breaker and outlet section.
mA RO
PDU.Gang[x].Current Measure Current provided by the breaker/section. For a double pole
breaker, it is calculated as the max of the two poles
current.
mA RO
PDU.Gang[x].EWEntity.Importance Parameter Energy Wise Importance - RW
PDU.Gang[x].EWEntity.Keyword String[31] Energy Wise Keyword - RW
PDU.Gang[x].EWEntity.Level Parameter Energy Wise Level - RW
PDU.Gang[x].EWEntity.Role String[31] Energy Wise Role - RW
PDU.Gang[x].GangID Constant Breaker ID = x(1,2,..) - RO
PDU.Gang[x].iGang String[15] Breaker/section silk-screened name.
Example: 'A' or 'B' ….
- RO
PDU.Gang[x].iName String[31] Breaker/section friendly name. - RW
PDU.Gang[x].InputID Constant Identify which Input is powering the group. This is useful
when the PDI is dual Input.
- RO
PDU.Gang[x].OverCurrent[1].Threshold Parameter mA RW
PDU.Gang[x].OverCurrent[3].Threshold Parameter mA RW
PDU.Gang[x].OverCurrent[4].Threshold Parameter mA RW
PDU.Gang[x].OverVoltage[1].Threshold Parameter Threshold cV RW
PDU.Gang[x].OverVoltage[2].Threshold Parameter Threshold cV RW
PDU.Gang[x].OverVoltage[3].Threshold Parameter Threshold cV RW
PDU.Gang[x].OverVoltage[4].Threshold Parameter Threshold cV RW
PDU.Gang[x].PeakFactor Measure Crest factor of the current provided by the breaker/section.
A double pole breaker is calculated as the max of the two
poles crest factor.
m% RO
PDU.Gang[x].PercentLoad Measure Percent load consumed by the breaker/section. It is the
ratio: current consumed / the nominal current.
% RO
PDU.Gang[x].PhaseID Constant Phase number that is connected to the breaker/section: 1,
2, or 3.
A double pole breaker is ij.
Ex: 12 if the 2 phases are L1 and L2.
- RO
PDU.Gang[x].Pole[1].ActivePower HideMeasure Active Power provided by the pole. dW RO
PDU.Gang[x].Pole[1].ApparentPower HideMeasure Apparent Power provided by the pole. dVA RO
PDU.Gang[x].Pole[1].Current HideMeasure Current provided by the pole. mA RO
PDU.Gang[x].Pole[1].PeakFactor HideMeasure Crest factor of the current provided by the pole. m% RO
PDU.Gang[x].Pole[1].PhaseID Constant Phase number that is connected to the pole: 1, 2, or 3. - RO
PDU.Gang[x].Pole[1].PowerFactor HideMeasure Ratio of active power / apparent power provided by the
pole of the breaker or outlet section.
m% RO
Table 8. ePDU CLI Objects (Continued)
XML Object Name Type Description Unit Access