Serial Interface Operation
Eaton ePDU G3 Operation Manual P-164000277—Rev 1 www.eaton.com/ePDU 75
PDU.Gang[x].Pole[1].ReactivePower HideMeasure Reactive Power provided by the pole. dVA
R
RO
PDU.Gang[x].Pole[1].Statistic[4].Energy HideMeasure Energy counter since last reset. As it is reset to 0, the
related timestamp is updated with the current RTC value.
Wh RO
PDU.Gang[x].Pole[1].Statistic[5].Energy HideMeasure Energy counter since last reset. When it is reset to 0 then
at the same time the related timestamp is updated with
the current RTC value.
Wh RO
PDU.Gang[x].Pole[1].Voltage HideMeasure Voltage Measured on the pole. cV RO
PDU.Gang[x].Pole[2].ActivePower HideMeasure Active Power provided by the pole. dW RO
PDU.Gang[x].Pole[2].ApparentPower HideMeasure Apparent Power provided by the pole. dVA RO
PDU.Gang[x].Pole[2].Current HideMeasure Current Power provided by the pole. mA RO
PDU.Gang[x].Pole[2].PeakFactor HideMeasure Crest factor of the current provided by the pole. m% RO
PDU.Gang[x].Pole[2].PhaseID Constant Phase number that is connected to the pole: 1, 2, or 3. - RO
PDU.Gang[x].Pole[2].PowerFactor HideMeasure Ratio of active power / apparent power provided by the
pole of the breaker or outlet section.
m% RO
PDU.Gang[x].Pole[2].ReactivePower HideMeasure Reactive Power provided by the pole. dVA
R
RO
PDU.Gang[x].Pole[2].Statistic[4].Energy HideMeasure Energy counter since last reset. As it is reset to 0, the
related timestamp is updated with the current RTC value.
Wh RO
PDU.Gang[x].Pole[2].Voltage HideMeasure Voltage Measured on the pole. cV RO
PDU.Gang[x].PowerFactor Measure Ratio of active power / apparent power provided by the
breaker or outlet section.
m% RO
PDU.Gang[x].PresentStatus.OverCurrent AlarmL1 0: No threshold triggered
1: Warning low threshold triggered
2: Critical low threshold triggered
3: Warning high threshold triggered
4: Critical high threshold triggered
- RO
PDU.Gang[x].PresentStatus.OverVoltage AlarmL1 0: No threshold triggered
1: Warning low threshold triggered
2: Critical low threshold triggered
3: Warning high threshold triggered
4: Critical high threshold triggered
- RO
PDU.Gang[x].PresentStatus.SwitchOnOff AlarmL1 - RO
PDU.Gang[x].PresentStatus.Tripped AlarmL1 0 : Breaker closed
1 : Breaker tripped (or open)
- RO
PDU.Gang[x].ReactivePower Measure Reactive Power provided by the breaker/section. For a
double pole breaker, the reactive power for the two poles
is combined.
dVA
R
RO
PDU.Gang[x].Statistic[3].Current Measure Current peak consumption since last reset.
As it is reset to 0, the related timestamp is updated with
the current RTC value.
When a value higher than the stored value is detected, the
stored valued is overwritten.
mA RO
Table 8. ePDU CLI Objects (Continued)
XML Object Name Type Description Unit Access