Serial Interface Operation
Eaton ePDU G3 Operation Manual P-164000277—Rev 1 www.eaton.com/ePDU 76
PDU.Gang[x].Statistic[3].ModuleReset Command Command to Reset the stat. This command puts 0 in the
max and saves the current value of Timer.
- RW
PDU.Gang[x].Statistic[3].Reset.Time Measure Timestamp saved when the stat reset is performed. s RO
PDU.Gang[x].Statistic[3].Time Measure Timestamp saved at the moment where the current peak
consumption is reset.
s RO
PDU.Gang[x].Statistic[4].Energy Measure Energy counter since PDU startup.
For a double pole breaker, it is calculated as the
accumulation of the two poles energy counter.
Wh RO
PDU.Gang[x].Statistic[4].ModuleReset Command Command to Reset the stat, This command does not put 0
in the counter, but saves the current value of Energy timer
into the data, Reset.Energy.
- RW
PDU.Gang[x].Statistic[4].Reset.Energy Measure Energy saved when the user resets the stat. Wh RO
PDU.Gang[x].Statistic[4].Reset.Time Measure Timestamp saved when the user resets the stat. s RO
PDU.Gang[x].Statistic[5].Energy Measure Energy counter since ePDU start.
If it's a double pole breaker, it is calculated as the cumul of
the two poles energy counter.
Wh RO
PDU.Gang[x].Statistic[5].ModuleReset Command Command to Reset the stat, this command does not put 0
in the counter but saves the current value of Energy timer
into the data ...Reset.Energy.
- RW
PDU.Gang[x].Statistic[5].Reset.Energy Measure Energy saved at the instant the user resets the stat. Wh RO
PDU.Gang[x].Statistic[5].Reset.Time Measure Timestamp saved at the instant the user resets the stat. s RO
PDU.Gang[x].Type Constant Type of gang:
1: Section of outlets (with 1 measurement)
2: Section of outlets (with 2 measurement, 1st method of
wiring CT, current is max of 2 pole measures)
3: Section of outlets (with 2 measurement, 2nd method of
wiring CT, current is sum of 2
- RO
PDU.Gang[x].Voltage Measure Voltage Measured on the breaker/section.
For a double pole breaker, it is the Li to Lj voltage.
cV RO
PDU.Input[1].ActivePower Measure Active Power Measurement.
It is the accumulation of 1 or 3 phase measures.
dW RO
PDU.Input[1].ApparentPower Measure Apparent Power Measurement.
It is the accumulation of 1 or 3 phase measures.
dVA RO
PDU.Input[1].ChangedStatus.FrequencyOutOfRange Timestamp s RO
PDU.Input[1].Frequency Measure Frequency Measurement. dHz RO
PDU.Input[1].Mode Constant Wiring Mode
0: Wye Measuring
1: Delta Measuring
2: Wye Current and Delta Measuring
- RO
PDU.Input[1].Phase.Count Constant Number of phase managed by the Input module. - RO
PDU.Input[1].Phase[x].ActivePower Measure Active Power Measurement. dW RO
PDU.Input[1].Phase[x].ApparentPower HideMeasure Apparent Power Measurement. dVA RO
PDU.Input[1].Phase[x].ChangedStatus.OverCurrent Timestamp Timestamp of last changing state of the alarm that has the
same name in the collection PresentStatus.
s RO
Table 8. ePDU CLI Objects (Continued)
XML Object Name Type Description Unit Access