EasyManua.ls Logo

Eaton ePDU G3 - Restarting the eNMC Module

Eaton ePDU G3
155 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Operation Overview
Eaton ePDU G3 Operation Manual P-164000277—Rev 1 www.eaton.com/ePDU 35
!
IMPORTANT
To power cycle the Eaton ePDU, remove the power cord from the power source and then plug
it back in.
Shutting Down the ePDU
To shut down the ePDU:
1. Shut down the connected devices according to the manufacturer’s recommended shutdown sequence.
2. Turn each circuit breaker to the Off position.
3. To remove power from the ePDU completely, disconnect the ePDU power cord from the power source.
Restarting the ePDU Network Management and Control (eNMC) module
You can restart the communications module using either a hardware or software method.
!
IMPORTANT
Restarting the eNMC module will not affect the output power or the connected equipment.
A software restart is triggered from the Serial interface or Web interface upon user action (see Figure 31). This
method is typically the better choice because all current settings in the communications module file system are
saved before restarting.

Table of Contents

Other manuals for Eaton ePDU G3

Related product manuals