Serial Interface Operation
Eaton ePDU G3 Operation Manual P-164000277—Rev 1 www.eaton.com/ePDU 67
Get all values of a family
pdu#0>get <short path>.*
where
<short path> = incomplete path name. A node must be complete.
Example 1
Example 2
pdu#0>get System.*
System.NetworkManagementSystem.Count
8
System.NetworkManagementSystem[x].HostName
../..
pdu#0>
Get Daisy-chained ePDU to Supervise or Retrieve Communication Status
pdu#0> pdu [x]
pdu#0>get <short path>.*
where
[x] = value 0 to 3 to indicate Host (0) or device (1, 2, or 3) to supervise; enter key to accept prompt ePDU
ID
<short path> = incomplete path name. A node must be complete.
Example 1
pdu#0>get System.DaisyChain.*
System.DaisyChain.DeviceId
0
System.DaisyChain.Position
1
System.DaisyChain.Status
1
System.DaisyChain.Count
1
pdu#0>
NOTE 1 The communication status is returned for the selected Device or Host by
System.DaisyChain.Status. The Status value is:
0: No Communication
1: Communication OK
2: Communication failed
3: Host conflict
4: Device conflict
NOTE 2 T
he Count command value is the number of ePDUs connected in the daisy-chain
configuration.