EasyManua.ls Logo

Eaton Magnefix MD4 - Page 17

Eaton Magnefix MD4
109 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Magnefix MD4
991.184 G01 03
17
Dimensions wall-mounted version
Panel name widths weight
Cable panel (including switch caps) 91 mm 15 kg
Busbar connection 91 mm 7.5 kg
Connecting panel 91 mm 4.5 kg
Busbar connecting panel (sectional panel including switch caps) 182 mm 19.5 kg
Protected panel with current transformers (including branch-circuit panel and switch caps) 230 mm 61.5 kg
Fuse panel with branch-circuit panel (including switch caps and fuse holders, excluding fuses)
230 mm 37.5 kg
Busbar connecting panel with SVS or HC switchgear 91 mm 9 kg
Height (overall height) 1487 mm
Depth with fuse panel 517 mm
Depth without fuse panel
(measured with a switch cap having an electromechanical indicator) 465 mm
Depth with protected panel (including earthing interlock) 605 mm (+ 27)
Calculation of width (example):
B= (K x 91) + (T x 230) + 72 where: K: number of cable panels
T: number of protected branches
Total switchgear width (B): number of panels (panel width) + 2 side plates.
Maximum switchgear width (B): 1404 mm (including 3
rd
support point) or maximum weight: 240 kg

Table of Contents

Related product manuals