Magnefix MD4
16
991.184 G01 03
2.3.2 Dimensions and weights
Dimensions upright version
Panel name width weight
Cable panel (including switch caps) 91 mm 15 kg
Busbar connection 91 mm 7.5 kg
Connecting panel 91 mm 4.5 kg
Busbar connecting panel (sectional panel including switch caps) 182 mm 19.5 kg
Protected panel with current transformers (including branch-circuit panel and switch caps) 230 mm 61.5 kg
Fuse panel with branch-circuit panel (including switch caps and fuse holders, excluding fuses)
230 mm 37.5 kg
Busbar connecting panel with SVS or HC switchgear 91 mm 9 kg
Height 1517 mm
Depth with fuse panel 517 mm
Depth without fuse panel
(measured with a switch cap having an electromechanical indicator) 423 mm
Depth with protected panel (including earthing interlock) 570 mm (+ 27)
Calculation of width (example):
B= (K x 91) + (T x 230) + 72 where: K: number of cable panels
T: number of protected branches
Total switchgear width (B): number of panels (panel width) + 2 side plates.
Maximum switchgear width (B): 1404 mm (including 3
rd
support point) or maximum weight: 240 kg.