EasyManua.ls Logo

Eaton Magnefix MD4 - Connecting Eaton 16 MM Transformer Cable to the Protected Branch of the Universal Clamps

Eaton Magnefix MD4
109 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Magnefix MD4
64
991.184 G01 03
3.8.5 Connecting Eaton 16 mm
2
transformer
cable to the protected branch of the
universal clamps
WARNING
Always earth the installation.
Never work on a live or partly live installation.
NOTE
These rubber sleeves are not resistant to cable
grease.
Eaton cable core clamps are only suitable for
connecting copper-cored plastic-insulated cable.
Eaton transformer cable.
Any length L is available to order.
Proceed as follows:
1. Insert the greased rubber sleeves (b) into the feed
apertures of the insulating conduits (a) at the top.
2. Slide the insulating conduit up the cable.
3. Connect the cable cores to the connection points using
the cable core clamps.
4. Make sure that the cable cores are correctly positioned
in the clamps. This is where the associated cross-
sectional area is stated (see detail).
5. Tighten the hexagon socket head screws
(torque 15 Nm (11 lbf)).
6. Ensure that the hexagon socket head screws are fitted
in the same direction angled forward (approx. 45°) for
all three phases.
NOTE
Re-tighten the cable core clamp hexagon socket
head screws after a time.
1
3..5
6

Table of Contents