67
3.9 Connection of plastic-insulated cables to
Protected panels
3.9.1 Plastic-insulated cable with copper
core up to 3 x 70 mm
2
WARNING
Always earth the installation.
Never work on a live or partly live installation.
Required materials
3 insulating conduits (a)
1 bag containing greased rubber sleeves (b)
3 sealing plugs (c)
3 protection tubes (d)
18 plastic screws (e)
3 cable core clamps (universal)
plastic cable clamps (j)
Cable box for plastic-insulated cable 3 x 70 mm
2
NOTE
Universal cable core clamps are only suitable
for connecting copper cable cores.
Terminate the cable cores in accordance with
the cable manufacturer’s instructions.
Universal cable core clamps, Cu, up to 70 mm
2