EasyManua.ls Logo

Eaton Magnefix MD4 - Connection of Plastic-Insulated Cables with Copper Cores, 3 X 95 MM up to 3 X; MM 2, Concentric Clamps

Eaton Magnefix MD4
109 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Magnefix MD4
58
991.184 G01 03
3.8.2 Connection of plastic-insulated cables
with copper cores, 3 x 95 mm
2
up to 3 x
240 mm
2
, concentric clamps
WARNINGG
Always earth the installation.
Never work on a live or partly live installation.
Required materials
3 insulating conduits (a)
1 bag containing greased rubber sleeves (b)
3 sealing plugs (c)
2 protection covers (d)
1 extension protection cover (e) (optional)
3 cable core clamps (concentric), each consisting of
1 connecting piece (1)
2 washers with hexagon socket head screws (2)
1 gland (3)
2 steel cable clamps or
2 plastic cable clamps
NOTE
Concentric cable core clamps are only suitable
for connecting copper cable cores.
Terminate the cable cores and the splice in
accordance with the cable manufacturer’s
instructions.
1A Concentric cable core clamps
Cu 95 to 240 mm
2
For cables with an aluminium core
Eaton cable core clamps are only suitable for connecting
cables with a copper core.
Aluminium cables are to be connected to the Magnefix
copper connection pins using copper/aluminium crimp
cable sockets.
This prevents stress corrosion.
Concentric crimp cable clamps consist of:
1 cable socket (1);
1 clamping ring with socket-head screw (2).
1B Crimp cable clamp, Al, up to 240 mm
2
Basically, any type of cable core clamp can be used,
provided it remains within the maximum permitted
dimensions of 40 x 110 mm when crimped.
1C Space available for cable sockets