Magnefix MD4
44
991.184 G01 03
3.6.3 PILC with copper or aluminium cores
up to 3 x 240 mm
2
, gland entry
WARNING
Always earth the installation.
Never work on a live or partly live installation.
Cable box for PILC up to 3 x 240 mm
2
, with soldering
gland.
Required components
For cables with a copper core
1 large cable box (b)
2 protection covers (c)
1 hose clip (d)
1 O-ring (f)
1 soldering gland (g)
3 cable core clamps (concentric), each consisting of
1 connecting piece (1)
2 washers with hexagon socket head screws (2)
1 gland (3)
2 steel cable clamps
For cables with an aluminium core
Eaton cable core clamps are only suitable for connecting
cables with a copper core.
Aluminium cables are to be connected to the Magnefix
copper connection pins using copper/aluminium crimp
cable sockets.
This prevents stress corrosion.
Concentric crimp cable clamps consist of:
1 cable socket (1);
1 clamping ring with socket-head screw (2).
Basically, any type of cable core clamp can be used,
provided it remains within the maximum permitted
dimensions of 40 x 110 mm when crimped.
1A Concentric cable core clamps Cu 95 to 240 mm
2
1B Crimp cable clamp, Al, up to 240 mm
2
1C Space available for cable sockets.