3.8 Connection of plastic-insulated cables to
C(able) and T(ransformer) panels
3.8.1 Plastic-insulated cable with copper
core up to 3 X 70 mm
2
, universal
clamps
WARNINGG
Always earth the installation.
Never work on a live or partly live installation.
Required materials
3 insulating conduits (a)
1 bag containing 3 greased rubber sleeves (b)
3 sealing plugs (c)
2 protection covers (d)
1 extension protection cover (e) (optional)
3 cable core clamps (universal)
2 steel cable clamps or
2 triple plastic cable clamps.
NOTE
Universal cable core clamps are only suitable
for connecting copper cable cores.
Terminate the cable cores and the splice in
accordance with the manufacturer’s
instructions.
Cable box for plastic-insulated cable 3 x 70 mm
2
Universal cable core clamps Cu to 70 mm
2