15. Slide the entry bushing (h) up the cable (a).
16. Slide the cable box (b) up the cable and then up the
entry bushing.
15, 16
17. Fix the cable in the cable clamp (c) at position (M)
previously marked.
Move the distance plates (b) until the centre of the
cable is exactly in line with the centre of the cable box.
Firmly tighten the cable clamp.
18. For copper-cored cables, depending on the core
diameter, refer to the procedure described in:
(3 x 70 mm
2
) Chapter 3.6.1, 13 to 23
(3 x 95 mm
2
) Chapter 3.6.2, 13 to 27
19. For cables with an aluminium core:
Once the crimp cable clamps have been placed, fix
them in accordance with the instructions. In this case
skip step 13.
17 .. 19
20. Firmly clamp the plastic entry bushing onto the cable
box using the hose clip (d) (torque 5 Nm (3.7 lbf)).
21. Firmly clamp the plastic entry bushing onto the cable
using the hose clip (d) (torque 5 Nm (3.7 lbf)).
22 Fill the cable box with grease (see Chapter 3.7).