3 Installation
3.6 Electrical Installation
76 DC1-S…20…, DC1-S…OE1 Variable Frequency Drives 05/21 MN040058EN www.eaton.com
Table 12 below shows which parameters can be used to configure the
function of the individual inputs and outputs.
Table 12: Parameters used to select and configure input and output functions
→
The control terminals’ functions and electrical parameters can
be changed with
• Parameter,
• DXC-EXT-… expansion modules (with IP20 degree of
protection only)
(→ section 4.7.2, “DXC-EXT-2RO output expansion”,
page 100 and → section 4.7.3, “DXC-EXT-2RO1AO output
expansion”, page 102).
→
The corresponding setting options can be found in
→ section 6.6, “Parameter”, page 142.
Connection
terminal
Function Format
(signal range)
Scaling
(Gain)
Offset Hysteresis
1 +24V Fixed – – – –
2 DI1 P-12/P15 – – – –
3 DI2 P-12/P15 – – – –
4 AI2/DI3
P-12/P15 P-47 – – –
5 +10 V Fixed – – – –
6 AI1/DI4 P-12/P15 P-16 P-35 P-39 –
70V Fixed – – – –
8 AO1/DO1 P-25 – – – –
90V Fixed – – – –
10 K13
P-18 – – – P-19/P-54/P-55
11 K14