User manual SEFELEC 5x Series  190   v1.06 
 
100 Mohm.km x 10 = 1,000 Mohm.km 
 
C) The insulation resistance value of a cable being a function following a time exponential law, it 
is important to make sense to the measured value, to indicate the duration of the measure-
ment. The units of the SEFELEC  5x  range  allow complying with this requirement with the 
built-in timer, able to measure times going from 1 second up to 3 hours.  
 
 
19.4.4.  MEASUREMENT VOLTAGE SELECTION 
 
The insulation resistance measurements intending to verify that materials or equipments comply 
with standard requirements, it is important to refer to these standards to select the voltage. The 
standard voltages are generally: 50, 100, 250, 500 VDC. 
In case of no standard, select a 100 VDC value. 
When measuring on capacitive specimens and when studying the voltage influence on the insu-
lation resistance values, it is important to start always with the lowest voltage and then to follow 
the measurements in increasing the voltage. A procedure in the reverse way could give incoher-
ent results. 
 
  DIELECTRIC STRENGTH TESTS 
The dielectric strength test is intended to stress components and sub-assemblies of electrical 
equipments and to check that the leakage lines either between points or between points and 
ground are correctly designed according to the used technology. 
The principle of a dielectric strength test is to apply a voltage (DC or AC) between defined points 
and after voltage stabilization, to check that the leakage current, created by breakdown phe-
nomena or breakdown discharges (in the air or in the insulating materials), is not greater than 
the nominal acceptable value. 
The default sanction is determined by the analyse of the shape, the amplitude and the holding 
time of the current supplied by the generator to the specimen under test and by comparison with 
a preset limit.