The ClassiFire automatic calibration process is as follows:
1. FastLearn: This stage lasts approximately 15 minutes. During FastLearn the
detector is not fully operational (accurate detection is not guaranteed).
2. Intermediate learn: This stage lasts approximately 24 hours. During
intermediate learn the detector is operational but is still fine tuning the
detection algorithm.
3. Normal: Normal indicates that initial environmental learning has ended and
that the detector is operating normally.
Note: Demo mode skips the intermediate learn mode and jumps from FastLearn
to normal mode. While active, Demo mode is indicated by the Warning LED and
on the display module LCD.
Software
The following software applications are available:
• PipeCAD: Models and verifies the performance of the pipe network design.
All pipework designs must be validated using PipeCAD.
• Remote: Configures modules during installation and during system
maintenance.
Contact your local distributor for more details on these applications.