Chapter 3: Configuration and Commissioning
ModuLaser Modular Aspirating Smoke Detector Installation Manual 61
To load a module configuration file:
1. Remove the display cover, insert a USB flash drive into the USB connector,
and replace the cover.
2. Select Device Settings from the Main menu, and then select Load/Save
Settings.
3. Select Load from File.
4. Select the device that you want to view or press F1 (Go To) to search for a
device by the device address.
Once the device has been selected, all compatible configuration files found
on the USB flash drive are displayed on the screen.
5. Select the configuration file to load, and then press Enter.
The new configuration is applied automatically.
Restoring the cluster configuration
The minimum or standard display module automatically saves the configuration
details for all detectors in the local cluster. If one or more detectors in the cluster
are replaced, the saved configuration can be quickly restored (maintaining the
original addresses).
To restore the cluster configuration
1. Select Device Settings from the Main menu, and then select Load/Save
Settings.
2. Select Restore Cluster Configuration, and then click OK.
The saved configuration is applied automatically.
Restoring the factory default settings
Use the Factory Default menu to restore a device to the original factory default
settings.
To restore to the factory default settings:
1. Select Device Settings from the Main menu, and then select Factory Default.
2. Select All Devices or List of Devices.
Selecting All Devices restores all modules on the loop. Selecting List of
Devices allows you to select specific modules to restore.
3. Press Enter to restore the selected devices.