EasyManuals Logo

Edwards ModuLaser User Manual

Edwards ModuLaser
105 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #91 background imageLoading...
Page #91 background image
Chapter 4: Maintenance and troubleshooting
ModuLaser Modular Aspirating Smoke Detector Installation Manual 85
Type
Message Description
Fault
Display Offline No display module found by the detector
Fault
Front Cover Removed Front cover removed
Fault
Input 1 Open Circuit Input 1 open circuit
Fault
Input 1 Short Circuit Input 1 short circuit
Fault
Input 2 Open Circuit Input 2 open circuit
Fault
Input 2 Short Circuit Input 2 short circuit
Fault
Battery Battery fault reported by the power supply
Fault
Mains Mains fault reported by the power supply
Fault
Power Supply Voltage
Low
Power supply voltage low
Fault
Internal Memory Internal memory fault
Fault
External Memory External memory fault
Fault
Reset from Watchdog The device has rebooted due to a watchdog failure
Fault
Date and Time Lost Date and time lost
Fault
Detector Not
Calibrated
Detector not calibrated
Fault
Incompatible Versions Incompatible versions found in the network
Fault
Subsystem Subsystem fault
Fault
No Pipe Calibration Pipe calibration data not found
Fault
Invalid Pipe
Calibration
Pipe calibration data invalid (new pipe calibration
required)
Warning
Disabled Device disabled
Warning
Installation Test The device is in installation test
Warning
User Interface LED
Test
The device is in LED test
Warning
User Interface TFT
Test
The device is in UI test
Warning
User Interface Keys
Test
The device is in Key test
Warning
Input Test The input is in test
Warning
Output Test The output is in test
Warning
Detection Aborted Detection aborted due to one or more of the following
faults: Front Cover Removed (detector), Fan Motor, Filter
Removed, Critical Temperature
Warning
FastLearn Start FastLearn in progress
Warning
Power Save Mode Power Save mode enabled
Warning
Flow Low Range Flow below absolute low range
Warning
Flow High Range Flow below absolute high range
Warning
Demo Mode Demo Mode enabled