Chapter 5: Technical specifications
ModuLaser Modular Aspirating Smoke Detector Installation Manual 89
Mechanical and environmental
Table 34: Mechanical
Dimensions
(W x H x D) 110.5 mm x 300 mm x 133.5 mm
(4.35 in. x 11.81 in. x 5.25 in.)
Weight (including backplane)
Display module
Detector module
1.18 kg (2.6 lb.)
1.57 kg (3.46 lb.)
Number of cable kn
ockouts
Top
Bottom
Back
3 x Ø 20.7 mm (0.815 in)
2 x Ø 20.7 mm (0.815 in)
2
Detector module orientation
Vertical or horizontal
IP
rating
Display module
Detector module
IP40
IP40
Flammability rating
UL94 V0
Dust filter replacement
Timed warning integrated.
Detector chamber maintenance
Subject to installation environment
Table 35: Environmental
Operating temperature
20ºC to +60ºC (0ºC to 38ºC UL268, cUL
and FM)
Storage temperature
20ºC to +60ºC
Relative humidity
+5 to 95% noncondensing (0 to 90% for UL/cUL
and FM)
IEC 61010-1 Pollution degree 1
IEC 61010-1 Installation Cat. II