2.1.3 Setup HART
®
communications
Daniel Ultrasonic Flow Meters are HART-capable devices utilizing the 4-20mA signal
Analog Output 1 on the CPU Module, in which the digital signal is sent from the field
device (Daniel Ultrasonic Flow Meter) to the host (PC running AMSTM Device Manager or a
Field Communicator). An external 24V power supply is required for the analog signal from
the CPU Module.
The HART Device Description application provides dynamic variables, device-specific
commands, universal commands and common practice commands in accordance with the
HART Communication Foundation. The Device Description defines the communication
details from the device to the host (e.g. menus for the Field Communicator, graphical
displays for AMS Device Manager and the device parameters - process variables, pressure,
temperature, diagnostics and three status alert groups - Failed, Maintenance and
Advisory). Refer to the Daniel 3410 Series Gas Ultrasonic Meters HART Field Device
Specification (P/N 3-9000-761) for details.
Also see, the HART Communications Foundation, AMS Device Manager and 475/375 Field
Communicator websites:
http://www.hartcomm.org/protocol/about/aboutprotocol.html
http://www2.emersonprocess.com/en-US/brands/amssuite/Pages/AMSSuite.aspx
http://www2.emersonprocess.com/en-US/brands/fieldcommunicator/475FC/Pages/
475FieldCommunicator.aspx
2.1.4
Setup the meter in a DeltaV System
Daniel 3410 Series Ultrasonic Flow Meters are compatible with DeltaV System
communications. The following are optional communications configurations of Daniel
Ultrasonic Flow Meters:
Serial connection for RS-232 or RS-485
Ethernet
HART
®
Modbus TCP/IP (requires a VIM card)
Refer to the Install Your Digital Automation System Manual for field wiring terminations,
I/O interface, power, and DeltaV control Network.
1. Access the DeltaV website hyperlink shown below.
2. Click Books Online under Quick Links.
3. Setup your user account and access the manual.
http://www2.emersonprocess.com/en-US/brands/DeltaV/Pages/index.aspx
Communications
10 3410 Series Gas Ultrasonic Flow meters