Install feature board in the Plantweb housing
Procedure
1. Apply a light coat of low temperature silicon grease to the SuperModule connector
O-ring.
2. Insert the SuperModule connector into the top of the SuperModule assembly.
Ensure the locking tabs are fully engaged.
3. Gently slide the feature board into the housing, making sure the pins from the
Plantweb housing properly engage the receptacles on the feature board.
4. Tighten the captive screws.
5. Attach the Plantweb housing cover and tighten so that metal contacts metal to
meet flameproof/explosion-proof requirements.
4.6.3
Terminal block
About this task
Electrical connections are located on the terminal block in the compartment labeled
“FIELD TERMINALS.” The terminal block may be replaced or upgraded to add transient
protection. Part numbers can be found in Service support.
Loosen the two captive screws (see Figure 4-12), and pull the entire terminal block out.
Figure 4-12: Terminal Blocks
Without optional process temperature
connections
With optional process temperature
connections
A
A
A. Captive screws
Procedure
1. Gently slide the terminal block into the housing, making sure the pins from the
Plantweb housing properly engage the receptacles on the terminal block.
2. Tighten the captive screws on the terminal block.
3. Attach the Plantweb housing cover and tighten so that metal contacts metal to
meet flameproof/explosion-proof requirements.
Reference Manual Operation and Maintenance
00809-0100-4803 October 2018
Emerson.com/Rosemount 123