RSTi-OM User Manual Section 3
GFK-3212A Jun 2021
Configuring 9
1.3.4 Specifications
Indicators/operating means
Setting the IP address and resetting to factory defaults
Electrical specifications
Max. 2 x 16 A per module
(Loop-through current via L-coded power supply)
Total current: max. 6.7 A per module
PROFINET IO with media redundancy protocol (MRP), Modbus/TCP, OPC UA, MQTT
8 x IO-Link Class A (X1 – X4)
Configurable as:
max. 8 IO-Link and 8 digital inputs
max. 16 digital inputs
max. 8 digital inputs and 8 digital outputs
short-circuit protected
Port 1: max. 1.6 A via L+ (pin 1)
Port 3: max. 1 A via L+ (pin 1)
Ports 2 and 4 to 8: max. 500 mA per port via L+ (pin 1)
Output rated operating
current
max. 200 mA per port via C/Q (pin 4)
Electromagnetic compatibility
EN 61000-6-2, EN 61000-6-4
Type 1 according to IEC 61131-2, EN 61131-9
CSA C22.2 No. 61010-1-12, UL 61010-1, IEC 61010-2-201
EN 61000-6-4, FCC part 15 subpart B, ICES-001, AS/NZS CISPR 11
EN 61000-6-2, EN 61131-2, EN 61131-9
-25 ... 60 °C (-13 ... 140 °F)
-40 ... 85 °C (-40 ... 185 °F)
Shock and impact
resistance
Mechanical specifications
Power Supply M12, L-coded
Fieldbus M12, D-coded
Inputs/Outputs M12, A-coded
Tightening torque,
fastening screws
Tightening torque, cable
gland
Tightening torque of
mounting screws