EasyManua.ls Logo

Emerson RSTi-OM - How to Use the Interface

Emerson RSTi-OM
157 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
RSTi-OM User Manual Section 7
GFK-3212A Jun 2021
Configuring IO-Link Devices
73
4. After successfully changing a parameter, the IO-Link Master responds with a command
executed notification.
Figure 59:IO-Link Master Response
5. This message means that the IO-Link device defines the entry as an invalid setting.
Figure 60: Invalid Setting Error
7.4.2 How to Use the Interface
Use the following procedure to edit parameters using the IO-Link Device ISDU Interface - Port.
Note: You may want to verify that the Automatic Download Enable for Data Storage option on the
Configuration | IO-Link Settings page is NOT set to On as this can cause unreliable results on the
corresponding port.
1. Click the + next to the IO-Link Device ISDU Interface to open the interface.
Figure 61: IO-Link Device
2. Enter the ISDU Block Index number (decimal) that you want to edit.
3. If applicable, enter the ISDU Sub-index (decimal).

Table of Contents