2.1.3 Connecting the Power
The IOLM provides M12 (5-poles) L-coded input and output power connectors. Use a 24VDC power
supply capable of the total output current required.
Note: Power connectors must have an approved cable or protective cover attached to the port
guarantee to IP67 compliance. If you require cables or protective covers, see the Emerson website.
Figure 5: IOLM Power Connectors Pinout
Power Output or Actuator
Power (Female)
IO-Link Master’s system electronics and IO-
Link devices
IO-Link Master’s system electronics and IO-
Link devices
Note: The IOLM requires a UL-listed power supply with an output rating of 24VDC.
Power Supply In - Maximum V
S and
V
A
IO-Link Connector Port 1
C/Q (Pin 4)
L+/L- Sensor Supply (Pins 1 and 3)
200 mA (Maximum) 1.6 A (Maximum)
IO-Link Connector Port 3
C/Q (Pin 4)
L+/L- Sensor Supply (Pins 1 and 3)
200 mA (Maximum) 1 A (Maximum)
IO-Link Connectors Ports 2 and 4 - 8
C/Q (Pin 4)
L+/L- Sensor Supply (Pins 1 and 3)
200 mA (Maximum)
500 mA (Maximum)/up to 1A Output Budget
Note: See IOLM Hardware Installation for
information about how to divide up the power
output between ports.
16A † (Maximum)
16A †† (Maximum)
† V
S
output available is determined by subtracting the following from the available input
current.
IO-Link Master module electronics current.
Total L+/L- current for all IO-Link ports.
Total C/Q current for all IO-Link ports.
†† V
A
output available is the same as the available U
A
input current.
You can use the following procedure to connect the IOLM to a power supply.
Note: Power should be disconnected from the power supply before connecting it to the IOLM.
Otherwise, your screwdriver blade can inadvertently short your power supply terminal connections to