RSTi-OM User Manual Section 3
GFK-3212A Jun 2021
Configuring 11
3. Turn each dial to the appropriate position using a small flathead screwdriver.
Figure 3: Rotary Switches
Note: The default setting is 000 as shown above.
4. The arrow points to switch location 0 is located at the 9:00 position. Turn the dial clockwise
to the appropriate setting.
5. Close the window and make sure that it snaps shut tightly.
Note: Failure to close the configuration window properly may compromise IP67 integrity.
Use the network configuration stored in the flash. The default network configuration
values are:
IP address = 192.168.11.202
Subnet mask = 255.255.255.0
IP gateway = 0.0.0.0
After completing the hardware installation, see Section 3: Configuring the IOLM with PAC
Machine Edition to set the network address using the web interface.
This is the last three digits in the IP address. This uses the first three numbers from the
configured static address, which defaults to 192.168.11.xxx.
Note: If the software is used to change the IP address to another range before setting the rotary
switches, the IOLM uses that IP address range. For example, if the IOLM is set to 10.0.0.250 and
the first rotary switch is set to 2, the IP address would be 10.0.0.200.
Reset to factory defaults. If the IOLM is set to 888 and the IP address is changed using
other methods, the IP address is returned to the default IP address if the IOLM is rebooted
or power cycled.
Use the network configuration values stored in the flash (reserved).
Setting the rotary switches to 998 configures the IOLM to use DHCP addressing.
Use the default IP address. If the IOLM is set to 999 and the IP address is changed using
other methods, the IP address is returned to the default IP address if the IOLM is rebooted
or power cycled.