RSTi-OM User Manual Section 8
GFK-3212A Jun 2021
Utilizing IOLM Features
81
Although you can make configuration changes using the web page, PROFINET IO configuration
parameters overwrite the values on the IO-Link Settings page. See IO-Link Port Settings (IO-Link Port
Module Parameters)for PROFINET IO configuration procedures.
Use this procedure to configure device validation.
1. Click Configuration | IO-Link Settings.
2. Click the EDIT button.
3. Select Compatible or Identical for the Device Validation mode.
Note: Identical Device Validation requires a device serial number to operate.
4. Click the GET ATTACHED button or manually complete the Vendor ID, Device, ID, and serial
number.
5. If the device does not have a serial number, you should not select Identical because the IOLM
requires a serial number to identify a specific device.
Figure 68: GET ATTACHED Button
6. Click the SAVE button. If the wrong or incompatible device is connected to the port, the IO-Link
port LED flashes red and no IO-Link activity occurs on the port until the issue is resolved.