Commissioning with the FF configuration program Cerabar M, Deltabar M, Deltapilot M
168 Endress+Hauser
Restart/RESTART
Options
Index: 16
Data type: unsigned8
Access: r, w
Select the reset mode.
Options:
ENP_RESTART: A restart is needed to accept the ENP configuration changes.
Run: Standard operating mode
Resource: This mode is not supported by Endress+Hauser.
Defaults: The device data and the links of the function blocks are reset to the factory
settings. The manufacturer-specific parameters of the Transducer Block are not
reset to the factory settings.
Processor: Warm start of device, processor restart.
Factory: The links of the function blocks, all FF-specific and resettable
manufacturer-specific parameters are reset to the factory setting.
Customer settings (user reset): If a new sensor is connected, sensor-specific
parameters are adapted to suit the new sensor. Resets the parameters to the as-
delivered state apart from the TAG number, linearization table, entries in the
operated hours counter, status history and format of the onsite display. The device
is restarted.
•Measurement AP: not effects.
Features/FEATURES
Display
Index: 17
Data type: bit string
Access: read only
Displays the additional functions supported by the device:
FEAT_REPORT
FEAT_FAILSAFE
FEAT_HARD_WR_LOCK
FEAT_MVC
See also this table, Feature Selection/FEATURE_SEL parameter description.
Feature Selection/
FEATURE_SEL
Entry
Index: 18
Data type: bit string
Access: wr for Auto,
OOS
Select the additional device functions. The additional functions that the device
supports are displayed in the Features/FEATURES parameter.
Cycle Type/
CYCLE_TYPE
Display
Index: 19
Data type: bit string
Access: read only
Displays the block execution methods supported by the device. See also this table,
Cycle Selection/CYCLE_SEL parameter description.
Cycle Selection/
CYCLE_SEL
Display
Index: 20
Data type: bit string
Access: wr for Auto,
OOS
Displays the block execution method used by the fieldbus host system. The block
execution method is selected by the fieldbus host system.
Possibilities:
Scheduled: cyclical block execution method
Block execution: sequential block execution method
Minimum Cycle Time/
MIN_CYCLE_T
Display
Index: 21
Data type: unsigned32
Access: read only
Displays the shortest MACROCYCLE supported by the device.
Factory setting:
3200
1
/
32
ms ( 100 ms)
Memory Size/
MEMORY_SIZE
Display
Index: 22
Data type: unsigned16
Access: read only
Displays the available configuration memory in kilobytes. This parameter is not
supported by Deltabar M 5x, Cerabar M 5x and Deltapilot M 5x.
Resource Block - standard parameters
Parameter Description