Commissioning with the FF configuration program Cerabar M, Deltabar M, Deltapilot M
194 Endress+Hauser
E. delta p status/
E_DELTA_P_STATUS
Display
Index: 106
Data type: unsigned8
Access: read only
Displays the status of the current input values for electr. delta P (Good,
Uncertain or Bad).
Factory setting:
Uncertain
E.delta p unit/
E_DELTA_P_INPUT_UNIT
Selection
Index: 107
Data type: unsigned8
Access: OOS
Select the unit of the electr. delta P input value.
Options:
• mbar, bar
•mmH2O
•inH2O, ftH2O
• Pa, kPa, MPa
•psi
•mmHg
•kg/cm
3
Factory setting:
mbar
Fixed ext. value/
ELECTRIC_DELTA_P_CONST
ANT
Entry
Index: 108
Data type: FLOAT
Access: OOS
Use this function to enter the constant value.
The value refers to E.delta p unit/E_DELTA_P_INPUT_UNIT.
Factory setting:
0.0
Min. meas. press./
PRESSURE_1_MIN_RESETAB
LE
Display
Index: 109
Data type: FLOAT
Access: read only
Displays the lowest pressure value measured (peakhold indicator). You can reset
this indicator by means of the Reset peakhold/
RESET_TRANSMITTER_OBSERVATION parameter.
Max. meas. press./
PRESSURE_1_MAX_RESETA
BLE
Display
Index: 110
Data type: FLOAT
Access: read only
Displays the highest pressure value measured (peakhold indicator). You can
reset this indicator by means of the Reset peakhold/
RESET_TRANSMITTER_OBSERVATION parameter.
Reset peakhold/
RESET_TRANSMITTER_OBSE
RVATION
Options
Index: 111
Data type: unsigned8
Access: OOS
You can reset the "Min. meas. press." and "Max. meas. press." indicators with this
parameter.
Options:
•Abort
•Confirm
Factory setting:
Abort
Sensor temp. (Cerabar/
Deltapilot)/
MEASURED_TEMPERATURE
_1
Display
Index: 112
Data type: FLOAT
Access: read only
Displays the temperature currently measured in the sensor. This can deviate
from the process temperature.
Pressure Transducer Block (Endress+Hauser parameters)
Parameter Description