Cerabar M, Deltabar M, Deltapilot M Commissioning with the FF configuration program
Endress+Hauser 195
DP_FLOW Transducer Block (only Deltabar M)
Temp. eng. unit/
TEMPERATURE_UNIT
Options
Index: 113
Data type: unsigned16
Access: OOS
Select the unit for the temperature measured values.
The setting affects the unit for the Sensor temp. (Cerabar/Deltapilot)/
MEASURED_TEMPERATURE_1 parameter.
Options:
•°C
•°F
•K
Factory setting:
°C
Device name str./
GENERIC_DEVICE_TYPE
Display
Index: 114
Data type: unsigned8
Access: read only
Displays the device type (Cerabar M, Deltabar M or Deltapilot M).
Format 1st value/
DISPLAY_MAINLINE_FORMA
T
Display
Index: 115
Data type: unsigned8
Access: read only
Displays the number of decimal places.
Options:
•x.x
•x.xx
• x.xxx
• x.xxxx
• x.xxxxx
DP_FLOW Transducer Block
Parameter Description
Device dialog/
DEVICE_DIALOG
Display
Index: 11
Data type: unsigned8
Access: read only
If configuration is unsuitable, this parameter displays a message indicating that
a configuration error is present. The message can indicate which parameter was
incorrectly configured.
Operator code/S_W_LOCK
Entry
Index: 12
Data type: unsigned16
Access: wr for Auto, OOS
Use this function to enter a code to lock or unlock operation.
Options:
•To lock: Enter a number the release code.
• To unlock: Enter the release code.
The release code is "0" in the order configuration. Another release code can be
defined in the Code definition/USER_S_W_UNLOCK parameter. If the user has
forgotten the release code, it can be made visible again by entering the number
sequence "5864".
Factory setting:
0
Lockstate/STATUS_LOCKING
Display
Index: 13
Data type: unsigned8
Access: read only
Displays the current locking status of the device or conditions that can lock the
device (hardware locking, software locking).
Pressure Transducer Block (Endress+Hauser parameters)
Parameter Description