Commissioning Cerabar PMP21 IO-Link
34 Endress+Hauser
Navigation Parameter → Application → Current output → Value for 4 mA (STL)
Description Assignment of the pressure value which should correspond to the 4 mA value.
It is possible to invert the current output. To do so, assign the pressure upper range value
to the lower measuring current.
Note Enter the value for 4 mA in the selected pressure unit anywhere within the measuring
range. The value can be entered in increments of 0.1 (increment depends on the
measuring range).
Options No selection. The user is free to edit the values.
Factory setting 0.0 or as per order specifications
Value for 20 mA (STU)
Navigation Parameter → Application → Current output → Value for 20 mA (STU)
Description Assignment of the pressure value which should correspond to the 20 mA value.
It is possible to invert the current output. To do so, assign the pressure lower range value
to the upper measuring current.
Note Enter the value for 20 mA in the selected pressure unit anywhere within the measuring
range. The value can be entered in increments of 0.1 (increment depends on the
measuring range).
Options No selection. The user is free to edit the values.
Factory setting Upper measuring limit or as per order specifications.
Pressure applied for 4mA (GTL)
Navigation Parameter → Application → Current output → Pressure applied for 4mA (GTL)