Description of device parameters Cerabar PMP21 IO-Link
60 Endress+Hauser
Description
L
WARNING
"Reset to factory settings" causes an immediate reset to the factory settings of the
order configuration (as-delivered state).
If the factory settings have been changed, downstream processes might be affected
following a reset (the behavior of the switch output or current output might be changed).
‣
Make sure that downstream processes are not started unintentionally.
The reset is not subject to additional locking, such as in the form of device locking. The
reset also depends on the device status.
Any customer-specific configuration carried out at the factory is not affected by a reset
(customer-specific configuration remains).
The following parameters are not reset when a reset is performed:
• LO Min value (minimum indicator)
• HI Max value (maximum indicator)
• Last Diagnostic (LST)
• Revisioncounter (RVC)
Note The last error is not reset in a reset.
Back-to-box
Navigation Parameter → System → Device Management → Back-to-box
Description Total reset (IO-link); this code resets all the parameters apart from:
• Revision-counter
• Peakhold indicator
Any simulation that may be running is terminated, the "F419" is displayed and a manual
restart is required.
14.4 Observation
The process data are transmitted acyclically.