Level measurement (via local operation and FieldCare) Cerabar S/Deltabar S/Deltapilot S FOUNDATION Fieldbus
112 Endress+Hauser
9.3.2 Calibration without reference pressure – dry calibration
Example:
In this example, the volume in a tank should be measured in liters. The maximum volume of
1000 liters (264 US gal) corresponds to a level of 4.5 m (15 ft). The minimum volume of 0 liters
corresponds to a level of 0.5 m (1.6 ft) since the device is mounted below the level lower-range
value. The density of the fluid is 1 kg/dm
3
.
Prerequisite:
The measured variable is in direct proportion to the pressure.
This is a theoretical calibration i.e. the height and volume values for the lower and upper
calibration point must be known.
!
Note!
See also Operating Instructions for Deltabar S (BA00301P) or Cerabar S (BA00302P), "Level
measurement" section or Deltapilot S (BA00372P), "Level measurement" section.
The values entered for EMPTY CALIB./FULL CALIB., EMPTY PRESSURE/FULL PRESSURE and
EMPTY HEIGHT/FULL HEIGHT must be at least 1% apart for the "Level easy height" level mode.
The value will be rejected with a warning message if the values are too close together. Further
limit values are not checked; i.e. the values entered must be appropriate for the sensor and the
measuring task so that the measuring device can measure correctly.
Due to the orientation of the device, there may be a shift in the measured value, i.e. when the
container is empty, the MEASURED VALUE parameter does not display zero. For information
on how to perform position adjustment, ä 142, Table 6: OPERATING MENU SETTINGS
POSITION ADJUSTMENT.
For a description of the parameters mentioned, see
ä 134, Table 2: GROUP SELECTION MEASURING MODE
ä 150, Table 9: OPERATING MENU SETTINGS BASIC SETUP "Level", LEVEL
SELECTION "Level easy height".
For a description of further relevant parameters, see
ä 183, Table 16: OPERATING MENU SETTINGS EXTENDED SETUP "Level"
ä 201, Table 28: OPERATING MENU PROCESSINFO PROCESS VALUES "Level".
Description
1 Select the "Level" measuring mode via the MEASURING
MODE parameter.
Local operation:
Menu path: GROUP SELECTION MEASURING
MODE
FieldCare:
Menu path: OPERATING MENU SETTINGS
BASIC SETUP MEASURING MODE
P01-PMC71xxx-19-xx-xx-xx-009
Fig. 25: Calibration without reference pressure –
dry calibration
1 See Table, Step 11.
2 See Table, Steps 13 and 14.
3 See Table, Steps 15 and 16.
2 If necessary, select the "Level easy height" level mode
using the LEVEL SELECTION parameter.
Local operation:
Menu path: GROUP SELECTION MEASURING
MODE "Level" LEVEL SELECTION
FieldCare:
Menu path: OPERATING MENU SETTINGS
BASIC SETUP MEASURING MODE "Level"
LEVEL SELECTION
3 Local operation:
Select the BASIC SETUP function group. Menu path:
GROUP SELECTION OPERATING MENU
SETTINGS BASIC SETUP
1000 l
0.5 m
4.5 m
0l
r =1
kg
dm
3