Gammapilot M FMG60 PROFIBUS PA Commissioning
Endress+Hauser 55
"Density value" (*1C)
Local display
Density value *1C
0.9963 g/cm3
This function is used to specify the density of the calibration point. The value must be
determined using a sample in the laboratory.
The temperature effect must be taken into account when entering the density value. The
density entered must refer to the temperature at which the pulse rate has been
determined. If the density and the pulse rate have been determined at different
temperatures, the density value must be corrected accordingly before it is entered.
"Calibration point" (*1D)
Local display
Calibration point *1D
Not used
Used
Clear
This function is used to specify whether the current calibration point is to be used or not.
Options:
• Not used
The calibration point is not used. It can be reactivated subsequently, however.
• Used
The calibration point is used.
• Clear
The calibration point is deleted. It cannot be reactivated subsequently.
"Absorption coefficient" (*1E)
Local display
Absorp. coeff. *1E
7.70 mm2/g
This function is used to display the absorption coefficient μ which results from the calibration
points that are currently active. The displayed value is used to check plausibility.
If only one calibration point is active, the absorption coefficient is not calculated and the
last valid value is used instead. The default value μ = 7.70 mm
2
/g is used during initial
commissioning and following a reset. This value can be changed by the user, however.