Operating menu Micropilot FMR10
54 Endress+Hauser
Factory setting An automatic Blocking distance (→ 53) of at least 0.1 m (0.33 ft) is configured as
standard. However, this can be overwritten manually (0 m (0 ft) is also permitted).
Automatic calculation of the Blocking distance = Empty calibration - Full calibration -
0.2 m (0.656 ft).
Each time a new entry is made in the Empty calibration parameter or Full calibration
parameter, the Blocking distance parameter is recalculated automatically using this
formula.
If the result of the calculation is a value < 0.1 m (0.33 ft), the Blocking distance of
0.1 m (0.33 ft) will continue to be used.
Level correction
Navigation Setup → Advanced setup → Level correction
Description The measured level is corrected by this value to compensate for a constant level error.
Level correction > 0: The level is increased by this value. Level correction < 0: The level is
decreased by this value.
User entry –25 to 25 m
Factory setting 0.0 m
Evaluation distance
Navigation Setup → Advanced setup → Evaluation distance
Description Extended signal search area. Is generally greater than the empty distance. If the signal is
found below the empty distance, '0' (empty) is indicated as measured value. Only for
signals, detected below the 'Evaluation distance', the error 'Echo Lost' is issued. e.g. flow
measurement in overflow weirs.
User entry 0 to 12 m
Factory setting 11.5 m