Micropilot FMR10 Operating menu
Endress+Hauser 57
"Current output" submenu
Navigation  Setup → Advanced setup → Current output
Output current
Navigation Setup → Advanced setup → Current output → Output current
Description Shows the actual calculated value of the output current.
User interface 3.59 to 22.5 mA
Damping output
Navigation Setup → Advanced setup → Current output → Damping output
Description Define time constant τ for the damping of the output current. Fluctuations of the
measured value affect the output current with an exponential delay, the time constant τ of
which is defined in this parameter. With a small time constant the output reacts
immediately to changes of the measrued value. With a big time constant the reaction of
the output is more delayed. For τ = 0 there is no damping.
User entry 0.0 to 300 s
Factory setting 1.0 s
Turn down
Navigation Setup → Advanced setup → Current output → Turn down
Description Using the turn down functionality it is possible to map a section of the measuring range to
the total range of the output current (4-20mA). The section is defined by the '4 mA value'
and '20 mA value' parameters. Without the turn down, the complete measuring range (0
to 100%) is mapped to the current output (4 to 20mA).
Selection Off
On
Factory setting Off