Micropilot FMR10 Operating menu
Endress+Hauser 59
Selection Off
4 mA
20 mA
Calculate
Reset
Factory setting Off
Trim value high
Navigation Setup → Advanced setup → Current output → Trim value high
Description Enter upper measured value for the trim (around 20 mA). After this value has been
entered: Select 'Trim' = Calculate. This initiates the recalibration of the current output.
User entry 18.0 to 22.0 mA
Factory setting 20.0 mA
Trim value low
Navigation Setup → Advanced setup → Current output → Trim value low
Description Enter lower measured value for the trim (around 4 mA). After this value has been entered:
Select 'Trim' = Calculate. This initiates the recalibration of the current output.
User entry 3.0 to 5.0 mA
Factory setting 4.0 mA