Loading...
3 Installation PROline Promag 50
26 Endress+Hauser
3.3 Installation instructions
3.3.1 Installing the Promag W sensor
!
Note!
Bolts, nuts, seals, etc. are not included in the scope of supply and must be supplied by
the customer.
The sensor is designed for installation between the two piping flanges:
Observe in any case the necessary screw tightening torques on Page 28 ff.
The mounting of additional ground disks is described on Page 27.
Fig. 16: Installing the Promag W sensor
Seals
Comply with the following instructions when installing seals:
Hard rubber lining additional seals are always necessary.
Polyurethane lining additional seals are recommended.
For DIN flanges, use only seals according to DIN 2690.
Make sure that the seals do not protrude into the piping cross-section.
"
Caution!
Risk of short circuit. Do not use electrically conductive sealing compound such as
graphite. An electrically conductive layer could form on the inside of the measuring tube
and short-circuit the measuring signal.
Ground cable (DN 25…2000)
If necessary, the special ground cable for potential equalisation can be ordered as an
accessory (see Page 85). Detailled assembly instructionsPage 57 ff.
F06-5xFxxxxx-17-05-xx-xx-000