PROline Promag 50 5 Operation
Endress+Hauser 67
5.4.3 Universal / Common practice HART commands
The following table contains all the universal and common practice commands
supported by Promag 50.
Command No.
HART command / Access type
Command data
(numeric data in decimal form)
Response data
(numeric data in decimal form)
Universal Commands
0 Read unique device identifier
Access type = read
none Device identification delivers information on the
device and the manufacturer. It cannot be
changed.
The response consists of a 12 byte device ID:
Byte 0: fixed value 254
Byte 1: Manufacturer ID, 17 = E+H
Byte 2: Device type ID, 65 = Promag 50
Byte 3: Number of preambles
Byte 4: Universal commands rev. no.
Byte 5: Device-specific commands rev. no.
Byte 6: Software revision
Byte 7: Hardware revision
Byte 8: Additional device information
Bytes 9-11: Device identification
1 Read primary process
variable
Access type = read
none Byte 0: HART unit code of the primary
process variable
Bytes 1-4: Primary process variable
Factory setting:
Primary process variable = Volume flow
! Note!
You can set the assignment of device varia-
bles to process variables using Command
51.
Manufacturer-specific units are represented
using the HART unit code “240”.
2 Read the primary process
variable as current in mA and
percentage of the set meas-
uring range
Access type = read
none Bytes 0-3: actual current of the primary
process variable in mA
Bytes 4-7: Percentage of the set measuring
range
Factory setting:
Primary process variable = Volume flow
! Note!
You can set the assignment of device variables
to process variables using Command 51.