PROline Promag 50 4Wiring
Endress+Hauser 53
Fig. 33: Connecting the transmitter (stainless-steel field housing). Cable cross-section: max. 2.5 mm
2
a Cable for power supply: 85…260 V AC, 20…55 V AC, 16…62 V DC
Terminal No. 1: L1 for AC, L+ for DC
Terminal No. 2: N for AC, L
− for DC
b Signal cable: Terminals Nos. 20–27
→ Page 54
c Ground terminal for protective conductor
d Ground terminal for signal cable shield
e Service adapter for connecting service interface FXA 193 (FieldCheck, FieldTool)
f Cover of the connection compartment
Fig. 34: Connecting the transmitter (wall-mount housing). Cable cross-section: max. 2.5 mm
2
a Cable for power supply: 85…260 V AC, 20…55 V AC, 16…62 V DC
Terminal No. 1: L1 for AC, L+ for DC
Terminal No. 2: N for AC, L
− for DC
b Signal cable: Terminals Nos. 20–27
→ Page 54
c Ground terminal for protective conductor
d Ground terminal for signal cable shield
e Service adapter for connecting service interface FXA 193 (FieldCheck, FieldTool)
f Cover of the connection compartment
b
c
d
a
2
1
L1 (L+)
N (L-)
f
b
a
e
– 27
– 25
– 23
– 21
+ 26
+ 24
+ 22
+ 20
F06-xxxxxxxx-04-06-xx-xx-006
1
2
cd
e
a
a
b
b
f
+
22
–
23
+
20
–
21
+
24
–
25
+
26
–
27
L1 (L+)
N (L-)
F06-xxxxxxxx-04-03-xx-xx-000