Proline Promag W 500
Endress+Hauser 19
PROFIBUS PA
Status and alarm
messages
Diagnostics in accordance with PROFIBUS PA Profile 3.02
Error current FDE (Fault
Disconnection Electronic)
0 mA
PROFIBUS DP
Status and alarm
messages
Diagnostics in accordance with PROFIBUS PA Profile 3.02
EtherNet/IP
Device diagnostics Device condition can be read out in Input Assembly
PROFINET
Device diagnostics According to "Application Layer protocol for decentralized periphery", Version 2.3
FOUNDATION Fieldbus
Status and alarm
messages
Diagnostics in accordance with FF-891
Error current FDE (Fault
Disconnection Electronic)
0 mA
Modbus RS485
Failure mode Choose from:
NaN value instead of current value
Last valid value
Current output 0/4 to 20 mA
4 to 20 mA
Failure mode Choose from:
4 to 20 mA in accordance with NAMUR recommendation NE 43
4 to 20 mA in accordance with US
Min. value: 3.59 mA
Max. value: 22.5 mA
Freely definable value between: 3.59 to 22.5 mA
Actual value
Last valid value
0 to 20 mA
Failure mode Choose from:
Maximum alarm: 22 mA
Freely definable value between: 0 to 20.5 mA