Proline Promag W 500
30 Endress+Hauser
PROFINET
A0032047
Pin Assignment
1 + TD +
2 + RD +
3 - TD –
4 - RD –
Coding Plug/socket
D Socket
Recommended plug:
• Binder, series 763, part no. 99 3729 810 04
• Phoenix, part no. 1543223 SACC-M12MSD-4Q
• When using the device in a hazardous location, use a suitably certified plug.
EtherNet/IP
A0032047
Pin Assignment
1 + Tx
2 + Rx
3 - Tx
4 - Rx
Coding Plug/socket
D Socket
Recommended plug:
• Binder, series 763, part no. 99 3729 810 04
• Phoenix, part no. 1543223 SACC-M12MSD-4Q
• When using the device in a hazardous location, use a suitably certified plug.
Service interface
Order code for "Accessories mounted", option NB: Adapter RJ45 M12 (service interface)
A0032047
Pin Assignment
1 + Tx
2 + Rx
3 - Tx
4 - Rx
Coding Plug/socket
D Socket
Recommended plug:
• Binder, series 763, part no. 99 3729 810 04
• Phoenix, part no. 1543223 SACC-M12MSD-4Q
• When using the device in a hazardous location, use a suitably certified plug.
Supply voltage
Order code for
"Power supply"
terminal voltage Frequency range
Option D DC24 V ±20% –
Option E AC100 to 240 V –15…+10% 50/60 Hz, ±4 Hz
Option I
DC24 V ±20% –
AC100 to 240 V –15…+10% 50/60 Hz, ±4 Hz