Proline Promag W 500
52 Endress+Hauser
3 ( 10)
A0029320
 31 Engineering unit in m(ft)
Replacement of cable gland on connection housing
Buried applications
A remote version with IP68 protection is optionally available for buried applications. The measuring
device satisfies the certified corrosion protection Im1/Im2/Im3 in accordance with EN ISO 12944. It
can be used directly underground without the need for additional protective measures. The device is
mounted in accordance with the usual regional installation regulations (e.g. EN DIN 1610).
A0029321
Environment
Ambient temperature range
Transmitter Standard: –40 to +60 °C (–40 to +140 °F)
Optional: –50 to +60 °C (–58 to +140 °F) (order code for "Test,
certificate", option JN "Ambient temperature of transmitter –50 °C (–
58 °F)")
Local display –20 to +60 °C (–4 to +140 °F), the readability of the display may be
impaired at temperatures outside the temperature range.
Sensor Process connection material, carbon steel:
–10 to +60 °C (+14 to +140 °F)
Process connection material, stainless steel:
–40 to +60 °C (–40 to +140 °F)
Mount the transmitter separately from the sensor if both the ambient
and fluid temperatures are high.
Liner Do not exceed or fall below the permitted temperature range of the liner .
If operating outdoors:
Install the measuring device in a shady location.
Avoid direct sunlight, particularly in warm climatic regions.
Avoid direct exposure to weather conditions.