Proline Promag W 800 Electrical connection
Endress+Hauser 29
Coil current cable
2 × 0.75 mm² PVC cable with common, braided copper shield (Ø 7 mm)
Conductor resistance: 37 km
Capacitance: core/core, shield grounded: 120 pF/m
Operating temperature: –20 to +80 °C (–4 to 176 °F)
Cable cross-section: max. 2.5 mm²
Test voltage for cable insulation: 1433 V AC r.m.s 50/60 Hz or 2026 V DC
A0003194
Fig. 17: Cable cross-section
a Electrode cable
b Coil current cable
1Core
2 Core insulation
3 Core shield
4Core jacket
5 Core reinforcement
6 Cable shield
7 Outer jacket
7.1.4 Preparing the electrode and coil current cable
Terminate the electrode and coil current cables as shown in the figure below (Detail A).
Fit the fine-wire cores with wire end ferrules (Detail B).
"
Caution!
Please note the following when terminating the cables:
For electrode cable:
Make sure that the ferrules do not touch the wire shield on the sensor side.
Minimum distance = 1 mm (exception “GND” = green cable).
For coil current cable:
Insulate one core of the three-core wire at the level of the core reinforcement. You only
require two cores for the connection.
1
2
3
4
5
6
7