Commissioning Proline Promass I 300 PROFINET
112 Endress+Hauser
Parameter Prerequisite Description Selection / User
interface / User
entry
Factory setting
Assign status The Switch option is
selected in the Operating
mode parameter.
The Status option is
selected in the Switch
output function parameter.
Select device status for switch
output.
Partially filled pipe
detection
Low flow cut off
Profinet Slot 24
*
Profinet Slot 25
*
Profinet Slot 26
*
Switch-on value The Switch option is
selected in the Operating
mode parameter.
The Limit option is selected
in the Switch output
function parameter.
Enter measured value for the
switch-on point.
Signed floating-point
number
Country-specific:
0 kg/h
0 lb/min
Switch-off value The Switch option is
selected in the Operating
mode parameter.
The Limit option is selected
in the Switch output
function parameter.
Enter measured value for the
switch-off point.
Signed floating-point
number
Country-specific:
0 kg/h
0 lb/min
Switch-on delay The Switch option is
selected in the Operating
mode parameter.
The Limit option is selected
in the Switch output
function parameter.
Define delay for the switch-on
of status output.
0.0 to 100.0 s
Switch-off delay The Switch option is
selected in the Operating
mode parameter.
The Limit option is selected
in the Switch output
function parameter.
Define delay for the switch-off
of status output.
0.0 to 100.0 s
Failure mode Define output behavior in
alarm condition.
Actual status
Open
Closed
Invert output signal Invert the output signal. No
Yes
* Visibility depends on order options or device settings
10.5.10 Configuring the relay output
The Relay output wizard guides the user systematically through all the parameters that
have to be set for configuring the relay output.
Navigation
"Setup" menu → Relay output 1 to n
RelaisOutput 1 to n
Switch output function
→  113
Assign flow direction check
→  113
Assign limit
→  114
Assign diagnostic behavior
→  114