Proline Promass I 300 PROFINET Technical data
Endress+Hauser 233
16.4 Output
Output signal PROFINET
Standards In accordance with IEEE 802.3
Current output 4 to 20 mA
Signal mode Can be set to:
Active
Passive
Current span Can be set to:
4 to 20 mA NAMUR
4 to 20 mA US
4 to 20 mA
0 to 20 mA (only if the signal mode is active)
Fixed current
Maximum output values 22.5 mA
Open-circuit voltage DC 28.8 V (active)
Maximum input voltage DC 30 V (passive)
Load 0 to 700 Ω
Resolution 0.38 µA
Damping Configurable: 0 to 999.9 s
Assignable measured
variables
Mass flow
Volume flow
Corrected volume flow
Density
Reference density
Temperature
Electronics temperature
Oscillation frequency 0
Oscillation damping 0
Signal asymmetry
Exciter current 0
The range of options increases if the measuring device has one or more
application packages.
Pulse/frequency/switch output
Function Can be set to pulse, frequency or switch output
Version Open collector
Can be set to:
Active
Passive
Passive NAMUR
Ex-i, passive
Maximum input values DC 30 V, 250 mA (passive)
Open-circuit voltage DC 28.8 V (active)
Voltage drop For 22.5 mA: ≤ DC 2 V
Pulse output
Maximum input values DC 30 V, 250 mA (passive)
Maximum output current 22.5 mA (active)