4. Switching on the power supply and configuring the device
Electronic inserts: FEI51, FEI52, FEI54, FEI55
BA300Fen015
Green LED 1 ( ready for operation), red LED 3 ( error indicated), yellow LED 6 (switching state)
--
++
++
--
FEI5xFEI5x
77
33
55
2211 33 44 55 66
BB CC
AA
LEDLED
onon
flashingflashing
ofofff
Function switch
position
Function – key + key Light emitting diodes (LED signals)
1 (green) 2 (green) 3 (red) 4 (green) 5 (green) 6 (yellow)
1
Operation Flashes
Operational
LED
On
(MIN-SIL)
Flashes
(warning/
alarm)
On
(MAX-SIL)
On/off/
flashes
Restore factory setting Press both keys for
approx. 20 s
On –> –> –> –> On/off/
flashes
2
Empty calibration Press On
(present)
On/off/
flashes
Full calibration Press On
(present)
On/off/
flashes
Reset:
Calibration and switch
point adjustment
Press both keys for
approx. 10 s
On –> –> –> –> On/off/
flashes
3
Switch point adjustment Press for < Press for > On
(2 pF)
Off
(4 pF)
Off
(8 pF)
Off
(16 pF)
Off
(32 pF)
On/off/
flashes
4
Measuring range Press for < On
(500 pF)
Off
(1600 pF)
On/off/
flashes
Two-point control s Press once On On/off/
flashes
buildup mode Press twice On On On/off/
flashes
5
Switching delay Press for < Press for > Off
(0.3 s)
On
(1.5 s)
Off
(5 s)
Off
(10 s)
On/off/
flashes
6
Self-test (function test) Press both keys Off
(inactive)
Flashes
(active)
On/off/
flashes
7
MIN-/MAX
Failsafe mode
Press for
MIN
Press for
MAX
Off
(MIN)
On
(MAX)
On/off/
flashes
SIL mode*
lock/unlock
Press both keys On
(MIN-SIL)
On
(MAX-SIL)
On/off/
flashes
8
Upload/download sensor
DAT (EEPROM)
Press for
download
Press for
upload
Flashes
(download)
Flashes
(upload)
On/off/
flashes
* Only in conjunction with FEI55 electronic insert (SIL).
1
7
3
5
_
+
Dc
Ds

Table of Contents

Related product manuals