Endress+Hauser
Electronic inserts: FEI53, FEI57S
BA300Fen016
LED 1 operational : Flashes at 5-second intervals.
LED 2 fault : The red LED flashes if there is a fault that you can correct.
LED 2 fault : The red LED lights up continuously if the device has a fault that cannot be corrected. See also
Page 78, "Troubleshooting".
AA
--
++
FEI5xFEI5x
0.....500pFStandard
0...1600pF
BB
11 22
LEDLED
onon
flashingflashing
ofofff
DIP switch Function
A
Standard
1)
: If the measuring range is exceeded no alarm is output.
A
: If the measuring range is exceeded an alarm is output.
B
Measuring range: The mesasuring range is between 0 to 500 pF.
Span: The span is between 5 to 500 pF.
B
Measuring range: The mesasuring range is between 0 to 1600 pF.
Span: The span is between 5 to 1600 pF.
A B
Standard
0.....500pF0.....500pF
0...1600pF0...1600pF