Electronic insert: FEI58
BA299Fen016
Green LED 1 ( operational status), red LED 2 ( fault message), yellow LED 3 (switching status)
FEI58
NAMUR
-
IEC 60947-5-6
+
MIN
>2,2mA
MAX
C
1
2
GD E F
3
C
A B
LED
on
flashing
off
DIP switches (C, D, E, F) Function
D
The probe is covered during calibration.
D
The probe is uncovered during calibration.
E
Switch point adjustment: 10 pF
E
Switch point adjustment: 2 pF
F
Switching delay: 5 s
F
Switching delay: 1 s
G
Failsafe mode: MIN
The output switches safety-oriented when the probe is uncovered (signal on
alarm). For use for dry running protection and pump protection for example
G
Failsafe mode: MAX
The output switches safety-oriented when the probe is covered (signal on
alarm). For use with overfill protection for example
Key Function
A B C
X Display diagnostic code
X Display calibration situation
X X Perform calibration (during operation)
X X Delete calibration points (during startup)
X Test key , (disconnects the transmitter from the switching unit)
C
C
MAXMIN
MAX