Each output card is supplied with an adhesive label that indicates the wiring connections of each option. To help identifying each
terminal, this label should be placed in the lower side of the meter case, beside the basic functions label.
NOTE: In case that the outputs are used to drive inductive loads, it is recommended to add an RC network between the coil
terminals (preferably) or between the relay contacts to limit electromagnetic effects.
7.1.5 Technical specifications
CARACTERISTICS
2 RELAYS
OPTION
4 RELAYS
OPTION
MAX.CURRENT (RESISTIVE LOAD) 8 A 5 A
MAX.POWER 2000 VA / 192 W 1250 VA / 150 W
MAX.VOLTAGE 250 VAC / 150 VDC 277 VAC / 125 VDC
CONTACT RESISTANCE Max. 3mΩ Max. 30mΩ
SWITCHING TIME Max 10ms Max 10mS
4 OPTOS NPN et 4 OPTOS PNP OPTION
MAX VOLTAGE 50 VDC
MAX CURRENT 50 mA
LEAKAGE CURRENT 100 µA (maxi)
SWITCHING TIME 1 ms (maxi)